Department of Mechanical Engineering

Coursework Assessment Brief Coversheet

Assessment Information

Module Code: MECH0071

Module name: Electrical Power Systems and Electrical Propulsion

Academic Year: 2025/26

Term: Term 1

Individual/Group: Individual

Word count or page count limit (if applicable): As written per question

% contribution to module: 35

Submission Date

Please see the submission portal on Moodle for the due date for this assessment.

Word count or page count penalty

Work that exceeds the word/page count by more than 10% will be reduced by 10 percentage points. This must not take the mark below the Pass Mark. Any material in addition to the 10% excess may not be taken into account in grading.

Eligibility for Delayed Assessment Permit (DAP)

This assessment is eligible for Delayed Assessment Permit.

Mitigation available: 5 working days.

Use of Generative AI

This assignment is classified as Category 2: AI tools can be used in an assistive role. Further details outlining what you can and cannot use AI for can be found in the full assessment brief.

Assessment Brief

Rubric:

(1) Answer all six questions

(2) The questions are not evenly weighted

(3) Upload your assignment to the submission portal on Moodle

(4) You will be marked on your ability to present the information clearly and at a standard suitable to the degree level

(5) You will be marked on your understanding and application of the technical content

(6) You will be marked on your ability to use the software tool PSCAD

(7) This coursework is AI Level 2

Question 1. Diode bridge circuit (3 marks)

Go to master library and find single phase AC source, set it to 100V 60Hz. Set the source ramp up time to 0. Go to HVDC, FACTS & Power electronics to find diodes. Remove the snubber circuit. Set the simulation duration to 0.1 seconds. Build up the diode bridge as shown in Figure 1. Set the capacitor value to 12mF.

Figure 1 - Diode Circuit Bridge

1. Upload a screen capture of your circuit diagram from PSCAD, make sure relevant parameters are clearly visible

2. Measure the instantaneous input voltage across the voltage source and the instantaneous output voltage across the resistive load. Upload an image of the two graphs.

3. Discuss the purpose and effect of changing the capacitor to 25 mF (max. 100 words).

Question 2. Equivalent transformer (3 marks)

Build an equivalent transformer as shown in Figure 2. Set the transformer power to 120MVA. Set the system frequency to 60Hz. Set the load to 350 Ohm resistive load. Add a multi-meter to measure the voltage and phase angle across the load.

Figure 2 - Equivalent Transformer

a. Upload a screen capture of your circuit diagram from PSCAD, make sure relevant parameters are clearly visible.

b. Measuring across the load, what is the:

• RMS voltage

• Power factor

c. Change the load to a 0.01H inductor, what is the:

• RMS voltage

• Power factor

d. Change the load to a 10mF capacitor, what is the:

• RMS voltage

• Power factor

Question 3. Faulted 3-phase network – 1 (3 marks)

The line diagram in Figure 3 shows a simple distribution network. A 3 phase 100MVA 6kV 50Hz star connected grounded generator having negligible source impedance, supplies a no-loss 6kV:33kV delta-wye connected transformer (also rated at 100MVA and grounded on the high voltage side) which in turn supplies a 3-phase load, with each phase having identical 7.5Ω resistance and 17mH inductance.

Figure 3 - Line Diagram of Distribution Network

A fault occurs on the high voltage side as shown in Figure 3. The fault is a Single-Line-to-Ground fault on phase A and occurs at 0.5 seconds for 0.05 seconds, after which the fault is presumed to have cleared. Construct the distribution network described above for a steady state 1-second duration simulation.

1. Upload a screen capture of your circuit diagram from PSCAD, make sure relevant parameters are clearly visible.

2. Upload a screen capture showing the plotted results of the voltage and current waveforms before, during, and after the fault occurs. Make sure it is presented to a readable scale.

3. Comment on and discuss the observed phenomena in the faulted waveforms (max. 100 words).

Question 4. Faulted 3-phase network – 2 (5 marks)

The same circuit as that in Question 3 now undergoes a different fault. Figure 4 below shows the current and voltage waveforms before, during, and after the fault.

Figure 4 - Faulted Voltage and Current Waveforms

1. From the waveforms, suggest what type of fault has occurred, provide justification for your suggestion using theory of faults (max. 200 words)

2. In the circuit from Question 3, place a breaker between the transformer and fault. Build a system within the circuit to represent the breaker operation. Note that the system should react to the fault current rather than be manually controlled (i.e. not using timed logic). Add a screenshot of your circuit and any other suitable screenshots, explaining its operation. You will be marked on the suitability and simplicity of the design (max. 200 words).

Question 5. Faulted 3-phase network (3) (9 marks)

Figure 5 shows a circuit diagram for a system comprising two generators, one motor, two transformers, and cable impedances (represented by ‘1’ and ‘2’). The equipment characteristics are detailed in Table 1.

Using the MVA method, calculate the fault level and fault current if a fault were to occur at location ‘Fault A’ and then at location ‘Fault B’ (the faults do not occur simultaneously). You must show your workings.

Suggest a mitigation strategy to reduce the risk such a fault occurring (max 300 words).

Figure 5 – Circuit Diagram (Q5)

Generators (star-connected)

Apparent power

15

MVA

Reactance

11

%

Voltage

3.3

kV

Frequency

50

Hz

Motor

Apparent power

10

MVA

Reactance

25

%

Voltage

3.3

kV

Step-down transformers

Apparent power

5

MVA

Resistance

2.1

%

Reactance

1.3

%

Turns ratio

7.5

-

Frequency

50

Hz

Cable impedance (1) per phase

Resistance

0.2

Reactance

0.45

Cable impedance (2) per phase

Resistance

1.2

Reactance

2.2

Table 1 – Equipment Characteristics

Question 6. Faulted Network Analysis (12 marks)

You have now used PSCAD to carry out fault analysis for a relatively simple system. Consider the following scenario:

Your company is installing standalone supply systems in remote areas not accessible to a distribution grid. These supply systems can be powered by wind, solar, geothermal or a combination of these sources. Your team has been given the task to determine the protection breaker ratings for the transmission line between the supply step up transformer and the low voltage distribution bus at the load end. Each source system is of the same basic design configuration but differ in terms of component specification and load capacity.

The design specification requires the following:

• A breaker at the HV side of the supply end transformer.

• Breakers at both the HV and LV sides of the distribution end transformer with the LV breaker being between the distribution end transformer and the distribution bus.

• Both transformers will be star – star with only the HV windings grounded.

• A bus interconnector between the main supply and a battery backup unit that is charged via the supply bus.

• If a fault occurs on the main supply the bus interconnector will open, and the battery backup unit will provide emergency power to critical loads.

There is a consultant engineer named Konrad Yearwood who might be able to offer some guidance, but his fees are high so make sure your questions are clear and concise as our budget is light.

1. Draw a circuit diagram for the system, showing all the locations that you would select to measure potential fault currents and explain why you have chosen those particular locations. Assume the resistive component of all impedances to be negligible. (4 marks)

2. Build an Excel Spreadsheet tool that can be used by the field engineers to determine any modifications that are necessary to the breaker design, should they measure different final impedance values to those assumed during system design. The tool will be valid for a single fault location in the system (of your choosing) and will calculate line-to-line, single-line-to-ground, and double-line-to-ground faults, based on the amended measurements. You can assume all per unit values are to the same reference bases. The tool must be user-friendly, and an instruction manual may be included (recommended) if you wish and will not be included in your final word count for this question. (8 marks)

(Max 1000 words)




热门主题

课程名

mktg2509 csci 2600 38170 lng302 csse3010 phas3226 77938 arch1162 engn4536/engn6536 acx5903 comp151101 phl245 cse12 comp9312 stat3016/6016 phas0038 comp2140 6qqmb312 xjco3011 rest0005 ematm0051 5qqmn219 lubs5062m eee8155 cege0100 eap033 artd1109 mat246 etc3430 ecmm462 mis102 inft6800 ddes9903 comp6521 comp9517 comp3331/9331 comp4337 comp6008 comp9414 bu.231.790.81 man00150m csb352h math1041 eengm4100 isys1002 08 6057cem mktg3504 mthm036 mtrx1701 mth3241 eeee3086 cmp-7038b cmp-7000a ints4010 econ2151 infs5710 fins5516 fin3309 fins5510 gsoe9340 math2007 math2036 soee5010 mark3088 infs3605 elec9714 comp2271 ma214 comp2211 infs3604 600426 sit254 acct3091 bbt405 msin0116 com107/com113 mark5826 sit120 comp9021 eco2101 eeen40700 cs253 ece3114 ecmm447 chns3000 math377 itd102 comp9444 comp(2041|9044) econ0060 econ7230 mgt001371 ecs-323 cs6250 mgdi60012 mdia2012 comm221001 comm5000 ma1008 engl642 econ241 com333 math367 mis201 nbs-7041x meek16104 econ2003 comm1190 mbas902 comp-1027 dpst1091 comp7315 eppd1033 m06 ee3025 msci231 bb113/bbs1063 fc709 comp3425 comp9417 econ42915 cb9101 math1102e chme0017 fc307 mkt60104 5522usst litr1-uc6201.200 ee1102 cosc2803 math39512 omp9727 int2067/int5051 bsb151 mgt253 fc021 babs2202 mis2002s phya21 18-213 cege0012 mdia1002 math38032 mech5125 07 cisc102 mgx3110 cs240 11175 fin3020s eco3420 ictten622 comp9727 cpt111 de114102d mgm320h5s bafi1019 math21112 efim20036 mn-3503 fins5568 110.807 bcpm000028 info6030 bma0092 bcpm0054 math20212 ce335 cs365 cenv6141 ftec5580 math2010 ec3450 comm1170 ecmt1010 csci-ua.0480-003 econ12-200 ib3960 ectb60h3f cs247—assignment tk3163 ics3u ib3j80 comp20008 comp9334 eppd1063 acct2343 cct109 isys1055/3412 math350-real math2014 eec180 stat141b econ2101 msinm014/msing014/msing014b fit2004 comp643 bu1002 cm2030